I Alarms
Multi CPU Errors (A)
I - 58
A01 MULTI CPU ERROR 3103
Details
- Although the number of modules has been set to 1 or greater number in the Ethernet module
count parameter setting, the number of actually mounted module is 0.
- The head I/O No. of the Ethernet network parameter differs from the I/O No. of the actually
mounted module.
Remedy
- Correct and write the network parameters.
- If the error occurs after correction, it suggests a hardware fault. Contact your local service
center.
Details
- In a multiple CPU system, the Q series Ethernet interface module under control of another
station is specified to the head I/O number of the Ethernet network parameter.
Remedy
- Delete the Ethernet network parameter of MELSECNET/H module under control of another
station.
- Change the setting to the head I/O number of the MELSECNET/H module under control of
the host station.
A01 MULTI CPU ERROR 3104
Details
- The Ethernet and MELSECNET/H use the same network number.
- The network number, station number or group number set in the network parameter is out
of range.
- The specified I/O No. is outside the range of the used CPU module.
- The Ethernet-specific parameter setting is not normal.
Remedy
- Correct and write the network parameters.
- If the error occurs after correction, it suggests a hardware fault. Contact your local service
center.
A01 MULTI CPU ERROR 3105
Details
- Though the number of CC-Link modules set in the network parameters is one or more, the
number of actually mounted modules is zero.
- The head I/O number in the common parameters is different from that of the actually mount-
ed module.
- The station type of the CC-Link module count setting parameters is different from that of the
actually mounted station.
Remedy
- Correct and write the network parameters.
- If the error occurs after correction, it suggests a hardware fault. Contact your local service
center.
Details
- In a multiple CPU system, the Q series CC-Link module under control of another station is
specified as the head I/O number of the CC-Link network parameter.
Remedy
- Delete the CC-Link network parameter of the Q series CC-Link module under control of an-
other station.
- Change the setting to the head I/O number of the Q series CC-Link module under control of
the host station.
A01 MULTI CPU ERROR 3106
Details
- The CC-Link link refresh range exceeded the file register capacity.
Remedy
- Change the file register file for the one refresh-enabled in the whole range.
Details
- The network refresh parameter for CC-Link is out of range.
Remedy
- Check the parameter setting.
A01 MULTI CPU ERROR 3107
Details
- The CC-Link parameter setting is incorrect.
- The set mode is not allowed for the version of the mounted CC-Link module.
Remedy
- Check the parameter setting.
A01 MULTI CPU ERROR 3300
Details
- The head I/O number in the intelligent function module parameter set on GX Configurator
differs from the actual I/O number.
Remedy
- Check the parameter setting.
A01 MULTI CPU ERROR 3301
Details
- The refresh setting of the intelligent function module exceeded the file register capacity.
Remedy
- Change the file register file for the one which allows refresh in the whole range.
Details
- The intelligent function module's refresh parameter setting is outside the available range.
Remedy
- Check the parameter setting.
A01 MULTI CPU ERROR 3302
Details
- The intelligent function module's refresh parameter is abnormal.
Remedy
- Check the parameter setting.
Zobrazit stránku 66
1 2 ... 62 63 64 65 66 67 68 69 70 71 72 ... 384 385

Komentáře k této Příručce

Darricknus 16 Feb 2024 | 10:14:18

Hello Guys, Glad to Join! :)

Fujitsu VFY:A5300MXAA2DE manuales

Manuales del propietario y guías del usuario para Cuadernos Fujitsu VFY:A5300MXAA2DE.
Ofrecemos 1 manuales en pdf Fujitsu VFY:A5300MXAA2DE para descargar gratis por tipos de documentos: Ficha de datos






Más productos y manuales para Cuadernos Fujitsu

Modelos Tipo de documento
VFY:E7510MXP51NL Ficha de datos   Fujitsu LIFEBOOK E751, 7 paginas
LKN:T9010M0002IT Ficha de datos   Fujitsu LIFEBOOK T901, 8 paginas
VFY:P701XMF011NC Ficha de datos   Fujitsu LIFEBOOK P701, 6 paginas
PCK:GBH-T730-81GB Ficha de datos   Fujitsu LIFEBOOK T730, 7 paginas
VFY:S7610MF011NL Ficha de datos   Fujitsu LIFEBOOK S761, 6 paginas
VFY:A5300MF211ES Ficha de datos   Fujitsu LIFEBOOK A530, 6 paginas
VFY:H2700WX071DE Ficha de datos   Fujitsu CELSIUS H270, 5 paginas
VFY:A5300MF142IT Ficha de datos   Fujitsu LIFEBOOK A530, 6 paginas
LKN:E7810M0001IT Ficha de datos   Fujitsu LIFEBOOK E781, 7 paginas
VFY:E7820MXP21FR Ficha de datos   Fujitsu LIFEBOOK E782, 7 paginas
VFY:N5320M2501FR Ficha de datos   Fujitsu LIFEBOOK N532, 6 paginas
VFY:A5320M2321FR Ficha de datos   Fujitsu LIFEBOOK A532, 5 paginas
VFY:E7800MF161NL Ficha de datos   Fujitsu LIFEBOOK E780, 8 paginas
FPCR47651 Ficha de datos   Fujitsu LIFEBOOK LH532, 6 paginas
LKN:H7100W0029FR Ficha de datos   Fujitsu CELSIUS H710, 7 paginas
VFY:NH532M3502BE Ficha de datos   Fujitsu LIFEBOOK NH532, 7 paginas
VFY:E7520M2501NC Ficha de datos   Fujitsu LIFEBOOK E752, 7 paginas
VFY:S7100MF041DE Ficha de datos   Fujitsu LIFEBOOK S710, 1 paginas
VFY:S7600MF121GB Ficha de datos   Fujitsu LIFEBOOK S760, 7 paginas
LKN:S7610M0008IT Ficha de datos   Fujitsu LIFEBOOK S761, 2 paginas